Customization: | Available |
---|---|
After-sales Service: | on-Site Technical Support |
Warranty: | 3 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Setting range | 6-phase AC(L-N) | 6x0…32A |
3-phase AC(L-N) | 3x0…64A | |
1-phase AC(LL-LN) | 1x0…192A | |
DC(L-N) | 6x0…±15A | |
Power | 6-phase AC(L-N) | 6x240VA at 32A |
3-phase AC(L-N) | 3x400VA at 64A | |
1-phase AC(LL-LN) | 1x750VA at 192A | |
DC(L-N) | 6x240VA at 15A | |
Accuracy | AC: ±2.5mA(≤0.5A), ≤0.05% (0.5~32A) | |
DC: ≤0.1% | ||
Resolution | 1mA |
Setting range | 4-phase AC(L-N) | 4x0…300V |
1-phase AC(L-L) | 1x0…600V | |
DC(L-N) | 4x0…±300V | |
Power | 4-phase AC(L-N) | 4x80VA at 300V |
1-phase AC(L-L) | 1x160VA at 600V | |
DC(L-N) | 4x80VA at 300V | |
Accuracy | AC: ±5mV(≤5V), ≤0.05% (5~300V) | |
DC: ≤0.1% | ||
Resolution | 1mV |
Binary Inputs | |
Number | 10 |
Input characteristics | idle contact or potential-free contact |
Threshold characteristics | "0":0-6V; "1":11V-250V |
Max. measuring time | 999999.999s |
Time accuracy | ≤0.1ms |
Time resolution | 0.1ms |
Binary Outputs | |
Number | 8 |
Type | idle contact |
Break capacity | 250VAC/0.5A, 250VDC/0.2A |
General Generators | |
Frequency | range: 0~1200Hz |
accuracy:<1mHz(0~65Hz),<2mHz(65~450Hz),<5mHz(450~1200Hz) | |
resolution: 0.001Hz | |
Phase | range: -360° ~+360° |
accuracy: 0.1° | |
resolution: 0. 1° | |
Harmonic | superposition order: 2~20 times |
distortion: ≤0.5% |