0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set

Product Details
Customization: Available
After-sales Service: on-Site Technical Support
Warranty: 3 Years

360° Virtual Tour

Diamond Member Since 2017

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
249
Year of Establishment
1999-07-27
  • 0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
  • 0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
  • 0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
  • 0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
  • 0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
  • 0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
Find Similar Products
  • Overview
  • Product Description
  • Specification
  • Packing & Delivery
  • Company Profile
  • FAQ
Overview

Basic Info.

Model NO.
Relaystar -H60
AC Current Output
6 Phases0-32A Per Phase
AC Voltage Output
4 Phases 0-300V Per Phase
AC Output Accuracy
0.05%
Frequency
DC-1200Hz
Power
1X750va 3X400va 6X240va
Harmonic
2~20 Times
GPS
in-Built
Binary Input
10 Channels
Input Method
10-250VDC or Free Contact
Binary Output
10
Output Method
AC(0.5A, 250V) / DC(0.2A, 250V)
Time Accuracy
±1ms
Laptop Control
Available
Transformer Test
Differential Protection
Transmission Line Protection
Distance Protection, Zero Sequence Protection
Transport Package
Standard
Specification
420*360*210
Trademark
Relaystar
Origin
China
HS Code
9030841000
Production Capacity
5000platform/Year

Product Description

0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
Product Description
RELAYSTAR-H60
The RELAYSTAR-H60 is the portable 6-phase protection relay test system for testing most types of modern multi-function protection relays, which can output 6-phase current(6x0…32A) and 4-phase voltage (4x0…300V).
The RELAYSTAR-H60 can be synchronized to perform end-to-end testing with the test sets allocated in different substations through its in-built GPS.
The RELAYSTAR-H60 can be operated by the RELAYSTAR software running on a laptop with Windows operating system.
The main features of Protection Relay Test System RELAYSTAR-H60 are as follows:
* 6-phase current(6x0…32A) + 4-phase voltage(4x0…300V) output
* Higher output accuracy(≤0.05% for AC output)
* End to end test via in-built GPS
* In-built monitoring and recording
* Abundant binary inputs and binary outputs
* Independent Aux. DC supply
* Powerful RELAYSTAR test software
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
Specification
Current Generator

Setting range
6-phase AC(L-N)
6x0…32A
3-phase AC(L-N)
3x0…64A
1-phase AC(LL-LN)
1x0…192A
DC(L-N)
6x0…±15A
Power
6-phase AC(L-N)
6x240VA at 32A
3-phase AC(L-N)
3x400VA at 64A
1-phase AC(LL-LN)
1x750VA at 192A
DC(L-N)
6x240VA at 15A
Accuracy
AC: ±2.5mA(≤0.5A), ≤0.05% (0.5~32A)
DC: ≤0.1%
Resolution
1mA
Voltage Generator

Setting range
4-phase AC(L-N)
4x0…300V
1-phase AC(L-L)
1x0…600V
DC(L-N)
4x0…±300V
Power
4-phase AC(L-N)
4x80VA at 300V
1-phase AC(L-L)
1x160VA at 600V
DC(L-N)
4x80VA at 300V
Accuracy
AC: ±5mV(≤5V), ≤0.05% (5~300V)
DC: ≤0.1%
Resolution
1mV
Binary Inputs
Number
10
Input characteristics
idle contact or potential-free contact
Threshold characteristics
"0":0-6V; "1":11V-250V
Max. measuring time
999999.999s
Time accuracy
≤0.1ms
Time resolution
0.1ms
Binary Outputs
Number
8
Type
idle contact
Break capacity
250VAC/0.5A, 250VDC/0.2A
General Generators
Frequency
range: 0~1200Hz
accuracy:<1mHz(0~65Hz),<2mHz(65~450Hz),<5mHz(450~1200Hz)
resolution: 0.001Hz
Phase
range: -360° ~+360°
accuracy: 0.1°
resolution: 0. 1°
Harmonic
superposition order: 2~20 times
distortion: ≤0.5%
Packing & Delivery
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
Transparency here reduces post-purchase inquiries. List package contents (e.g., product, USB-C cable, multilingual manual, warranty card) and highlight sustainable packaging (e.g., "100% recyclable materials"). Clarify shipping timelines by region (e.g., "EU: 5–7 business days," "APAC: 10–15 business days") and costs (e.g., "Free shipping on orders over $50"). State customs/duty responsibilities (e.g., "Duties calculated at checkout") and offer damage protection (e.g., "Free replacements for shipping-damaged items"). Add tracking instructions or icons (e.g.,) for clarity.
Company Profile
HAOMAI ELECTRIC POWER AUTOMATION
HAOMAI ELECTRIC POWER AUTOMATION, established in 1999 and headquartered in Wuhan, China, specializes in developing and manufacturing electrical power test and measurement instruments. Our products are widely used in power grids, petrochemicals, metallurgy, railways, coal mines, research institutes, and large-scale enterprises.
Key product lines include Protection Relay Test Systems, CT/PT Analyzers, Battery Load Testers, Transformer Testing Equipment, Circuit Breaker Analyzers, and Partial Discharge Detectors.
HAOMAI maintains strict quality control standards with ISO 9001:2015, ISO 14001:2015, and OHSAS 18001:2007 certifications 2. The company operates advanced laboratories, including the RELAYSTAR lab, equipped with precision instruments like Agilent 34401A meters and CLOU Standard Power Sources.
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
0.05% Accuracy 4 Voltage 6 Current High Voltage Relay Test Set
FAQ
Q1: Who Should Use Relaystar-H60 and What Are Its Applications?
The Relaystar-H60 is designed for protection relay testing professionals1 including utility engineers, field technicians, and system integrators. This 6-phase relay tester is ideal for:
  >>Testing multifunctional protection relays in substations
  >>Conducting end-to-end tests using built-in GPS synchronization
  >>Verifying relay performance in complex power system scenarios

Q2: Why Choose Relaystar-H60 Over Other Relay Testers?
The H60 stands out with:
High precision outputs (≤0.05% AC accuracy) – critical for compliance testing
6x32A current + 4x300V voltage output capacity to simulate real-world fault conditions
Built-in monitoring/recording functions for comprehensive test analysis
Portable design with powerful RELAYSTAR software for streamlined workflows

Q3: Why Select Haomai as Your Relay Testing Partner?
Haomai delivers:
Industry expertise with dedicated relay testing solutions1
Cutting-edge R&D evidenced by GPS-synchronized testing technology
Global support network through technical centers and certified partners
Comprehensive product range covering IEC 61850, CT/PT, and primary injection testing

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier